Measurements 9410 series
Related Topics
Apparent, active and reactive power (PQS)
Configuring conditional energy using ION Setup
You can enable and configure conditional energy settings using ION Setup.
When configuring your meter, the configuration interface may show all of the possible
ports, regardless of what is physically available on your meter.
One of your device’s digital inputs must be connected and configured to define when
conditional energy is accumulated.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Energy Applications > Digital Input Based. Review the digital inputs
assigned to applications to help ensure there are no conflicting usages.
4. Select Conditional Energy and click Edit. The Conditional Energy Setup screen
is displayed.
5. Select Enabled to enable the conditional energy feature.
6. Click Select to define the digital input. The input’s state determines whether
conditional energy is accumulated. When this digital input is on, conditional energy
is accumulated.
NOTE: It is recommended to set Assigned Input to No Connection to disable the
conditional energy feature by removing any port associations.
7. Click OK to save your configuration.
Trending and forecasting overview
Trending and forecasting is a feature on your device that predicts the next set of
measured or calculated data by plotting and analyzing trends in historical data.
Trending and forecasting data is a useful tool to help analyze changes in load and
power quality and forecasting values such as demand. For your meter’s trending and
forecasting feature to work, you only need to give the meter time to accumulate data.
Trending and forecasting implementation
Data used for trending and forecasting can be logged for specific intervals.
Data used is logged for the following intervals:
Every hour for the last 24 hours
Every day for the last month
Every week for the last 8 weeks
Every month for the last 12 months
The following parameters are configured for trending and forecasting using ION Setup:
kW sd del-rec (demand) Freq (frequency)
Vll ab I a mean
Vll bc I b mean
7EN05-0336-01 147