Specifications 9410 series
LEDs
Energy pulsing LEDs (visible and infrared) located on top of meter
Type Visible orange, infrared
Wavelength 600 609 nm (orange) 825 925 nm (infrared)
Maximum pulse rate 42 69 Hz (based on line frequency)
EMC (electromagnetic compatibility)
Product standards IEC 62052-11
IEC 61326-1
Immunity to electrostatic discharge IEC 61000-4-2
Immunity to radiated fields IEC 61000-4-3
Immunity to fast transients IEC 61000-4-4
Immunity to surges IEC 61000-4-5
Immunity to conducted disturbances IEC 61000-4-6
Immunity to voltage dips and
interruptions
IEC 61000-4-11
Immunity to magnetic fields IEC 61000-4-8
Immunity to ring waves IEC 61000-4-12
Immunity to conducted disturbances, 2 -
150 kHz
CLC/TR 50579
Radiated and conducted emissions FCC part 15 Class B, EN55011, EN55022 Class B, ICES-003 Class B
Surge withstand capacity (SWC) ANSI C37.90.1
Mechanical compliance
Vibration IEC 60068-2-6
Shock IEC 60068-2-27
Safety
Safety construction IEC/EN 61010-1 ed.3, CAT III, 400 VLN / 690 V LL
UL 61010-1 ed.3 and CSA-C22.2 No. 61010-1 ed.3, CATIII, 347 V LN /
600 V LL
IEC/EN 62052-11, Protective Class II
Ethernet communications
Number of ports 2 (the second connector functions as an Ethernet switch for networking devices)
Maximum cable length 100 m (328 ft), per TIA/EIA 568-5-A
Cable type CAT5/5e UTP (use unshielded connector only)