9410 series Specifications
Digital outputs
Maximum load voltage 30 V AC / 60 V DC
Maximum load current 75 mA
ON resistance 13 40 Ω at 25 °C (77 °F)
Signal type Continuous or pulse
Pulse frequency 25 Hz
Digital inputs
Number 3
Type Externally excited
Event timestamp accuracy ± 1 ms
Maximum voltage 30 V AC / 60 V DC
Pulse frequency 25 Hz
IRIG-B IRIG-B00x format (unmodulated IRIG-B time code)
Coded expressions 0 to 7 are supported but the year data is not used.
Response time 20 ms
Minimum pulse width 20 ms
Current draw ON: 2.5 mA
OFF: 0.5 mA
Environmental characteristics
Operating temperature -25 ºC to Max temp (-13 ºF to Max temp)
Maximum operation temperature is based on the quantity and type of attached option modules. See
Maximum operating temperature, page 166.
Storage temperature -40 to 85 °C (-40 to 185 °F)
Humidity rating 5 95% RH non-condensing
Maximum dewpoint: 37 °C (99 °F)
Pollution degree 2
Altitude < 3000 m (9843 ft)
Location/mounting Not suitable for wet locations
For indoor use only
Must be permanently connected and fixed
Maximum operating temperature
Max temp 948M2DO6DI
Digital (2 out, 6 in)
948M2AO4AI
Analog (2 out, 4 in)
70 ºC (158 ºF) 0 4 0,1
70 ºC (158 ºF) 0 2
60 ºC (140 ºF) 1, 2 2 4
166 7EN05-0336-01