Communications 9410 series
NOTICE
DATA LOSS
Failure to follow these instructions can result in equipment damage.
Record your device's user and password information in a secure location.
1. Start ION Setup.
2. Open the Setup Assistant for your device.
3. Select Communications > Network Settings and click the TCP/IP tab.
4. Select a setting and then click Edit. Configure the settings (for example, IP
address, subnet or gateway) to match your communications system.
Parameter Value Description
Ethernet device name configurable This name is associated with
your meter when using DPWS.
By default, it is the meter type
and the last 6 characters of its
MAC address.
Enable IPv6 Yes/no Specifies if IPv6 is enabled or
disabled.
IP address Contact your local network
administrator for parameter
values.
The Internet protocol address
of your device.
SubnetMask The Ethernet IP subnetwork
address of your network.
Gateway The Ethernet IP gateway
address of your network.
Rx timeout configurable Specifies the number of
seconds the meter waits for
communication
acknowledgments.
Modbus TCP Idle Timeout configurable Specify number of seconds the
meter waits before
disconnecting an idle Modbus
TCP connection.
Modbus Gateway Disabled/COM1 Specify the port on which
Modbus Gateway sends/
receives Modbus TCP
requests.
NOTE: For Modbus gateway to
function properly, the serial port
protocol must be set to Modbus
Master.
MAC address Read-only The media access control
(MAC) address is factory set
and is for reference only.
5. Click the Protocols tab.
6. Select a protocol and then click Edit. Select whether the protocol connection
requests are accepted by the meter, and configure the port number. Existing
connections are not affected, but any new connections must comply with the
meter’s latest settings.
NOTE: The protocol port number is not configurable on all protocols.