9410 series Communications
5. Select the desired meter value from those available. If the value you want is not
shown, select Show all available registers.
6. Select an IEC 61850 leaf to associate with the meter data, and click >> to map the
value. Click << to unmap values. Click OK to send and save your changes to the
meter.
Configuring digital outputs for IEC 61850 control using ION Setup
You can configure your digital outputs so that they can be used for non-critical control
via IEC 61850.
Your meter has a comprehensive default implementation of IEC 61850 which meets
the needs of most systems with only basic configuration. You can customize this
implementation so that IEC 61850 can be used to control your meter’s digital outputs;
this is an advanced procedure that requires in-depth knowledge of your meter, its
underlying architecture, and the system in which it is installed.
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Do not use this device for critical control or protection applications where human or
equipment safety relies on the operation of the control circuit.
1. Start ION Setup.
2. Connect to your meter in advanced mode.
3. Navigate to the GGIO Onboard folder and double-click on the module in the
righthand pane.
4. Select the Setup Registers tab.
5. Select the SPCS Control Mode register that corresponds to the digital output you
want to control through IEC 61850 and click Edit. A dialog appears.
6. Select IEC 61850 CTLVAL from the dropdown list and click OK.
7. Select the Inputs tab.
8. Select the digital output Status register for the digital output that you want to control
through IEC 61850. Click Delete.
NOTE: This digital input register must be deleted in order to prevent a circular
reference that will cause the affected modules to go offline.
9. Click Send to send your changes to the meter.
10.Select the Setup Registers tab and confirm that the Digital Output module’s setup
registers are appropriately configured.
11.Select the Inputs tab.
12.Select the Source register and click Edit.
13.Navigate to the IEC 61850 GGIO Onboard folder and select the SPCS.stVal output
register that corresponds to the digital output.
14.Click OK and Send to save your changes to the meter.
See the ION Reference, available from www.usa.siemens.com/pds, for information
about the IEC 61850 GGIO and Digital output modules.