Time and timekeeping 9410 series
7. For SNTP/NTP time synchronization, you must also enter the following information
under Communications > Network Settings > NTP:
Parameter Value Description
Enable NTP Time Sync NTP, SNTP, No NTP: specifies NTP time synchronization.
SNTP: specifies SNTP time synchronization.
NOTE: SNTP is recommended for revenue-related applications.
No: neither NTP nor SNTP time synchronization are used.
NTP Time Sync Interval Numeric value or elapsed
interval value
Specifies how often the meter synchronizes over SNTP.
NOTE: This parameter is not used for NTP.
NTP Event Logging
Threshold (NTP only)
1000 to 1000000 Specifies the minimum time difference (in milliseconds) for a time synchronization to
be logged as an event.
This parameter can be configured to help prevent the meter’s event log from being
flooded with time synchronization events.
NTP Server Server IP address or
domain name
Specifies the IP address (or fully qualified domain name if DNS is active) of the SNTP
or NTP server.
8. For serial GPS time synchronization, you must also enter the following information
under Communications > Serial settings:
Parameter Description
Protocol Select the GPS setting that matches your GPS receiver.
Baud rate The recommended baud rate for GPS time synchronization is 9600 bps.
Serial port The recommended stop bits/parity for GPS time synchronization is 8N1.
7EN05-0336-01 81