21 
AOP Operating Instructions – Issue 07/05 
6SE6400-5AP00-0BB0 
¾ Start 
¾ Stop 
 
The 
 key does not function in the broadcast mode since parameters cannot 
be edited on a global basis. 
The 
 and   keys still function in broadcast mode. For example, it would 
be possible to change the speed of the motor simultaneously across all 
connected inverters. 
4.2.2 Communications Failure 
If at any time, communications fail between the AOP and a connected slave 
inverter, a ‘Slave Error’ warning screen is displayed. This screen will indicate 
which slave inverter is not working correctly. 
The 
 key must be pressed to acknowledge the fault condition. 
Should the fault condition occur again, then the user will be returned to the Main 
Menu and will not be allowed to enter the ‘local’ Operate mode. 
5  Selecting the Operating Mode 
The Mode Menu allows the user to select the required operating mode of the 
AOP. The modes supported by the AOP are listed below: 
¾ LOCAL 
¾ MASTER 
¾ INTERNAL 
¾ SLAVE 
¾ PC mode 
¾  MM3 Upload (see Section 5) 
 
To exit a selected mode either follow the on screen instruction or select Mode 
from the top level menu and change to a different mode of operation. 
 
A summary of the various modes and their limitations is contained in the table 
below. 
When changing the mode of the AOP, the user is always presented with a 
confirmation screen. 
Press 
 to confirm the selected mode. 
Press 
 to return to the Main Menu. 
 
LOCAL MASTER INTERNAL SLAVE 
PC 
Mode 
MM3 
Upload 
Operate Operate         
Diagnostics Diagnostics Diagnostics       
Parameters Parameters Parameters       
Mode Mode Mode Mode Mode Mode 
Upread Upread       Upread 
Download Download         
Language Language Language      Language 
Setup Setup Setup     Setup 
Timer Timer Timer       
 Engineering    
 
The various modes are selected from the Main Menu using the following 
procedure: