Control via the operator panel
4.6 Menu commissioning / service
Cabinet Modules Operator Panel AOP30
54 Operating Instructions, 04/2014, A5E03263551A
Daylight-saving time changeover
The time does not automatically change over to daylight-saving time.
●
Selection is only possible if synchronization is set to "None" or "AOP -> Drive".
The time is then automatically set to summer or winter time.
After the changeover - for synchronization "AOP -> Drive" - synchronization is
immediately carried out, irrespective of the synchronization interval set.
Changes to the synchronization must be saved with "Save".
In this menu, the date format can be set:
●
: North American date format
Using the setting option "User-defined DO name" "No/Yes", you can toggle the display of the
DO name between the standard abbreviation (e.g. A_INF, VECTOR; CU_S) and a DO name
of your own choice (e.g. Infeed_1, Motor_1).
The "User-defined DO name" stored in parameter p0199 is displayed instead of the
standard DO abbreviation.
●
The standard DO abbreviation is displayed.
Normalization to motor current
The reference variable for the bar-type display of parameter r0027 (smoothed absolute
current actual value) can be changed over in the operating screen forms in this menu.
Normalization to motor current
The bar-type display of parameter r0027 in the operating screen form is displayed
referred to parameter p0305 (rated motor current).
●
The bar-type display of parameter r0027 in the operating screen form is displayed
referred to parameter p2002 (reference current).