BC8001A Installation and Operating Instruction
Page 35/49
Editable Parameters of Different Point
Point Type
Parameter
Default Value
Optional Value
BDS051(A) Smoke Detector Sensitivity Standard 1: Low
2: Standard
3: High
BDS221(A) Output Module
Supervision Time:
30s 30…600 Seconds
Supervision time: Define the waiting-for-
confirmation time of activated output
equipment (if the controller still cannot
receive a confirmation signal by timeout,
it will display active with no confirma-
tion. Otherwise it will display active
with confirmation”.)
Work Mode Steady
BDS132(A) Alarm Input
BDS132(A) Tech Input
Alarm Input
Technical Input
Dry Contact Alarm Input
Dry Contact Technical Input
Filter 3 1…7
NAC Work Mode Steady Steady
Pulse(60 per min)
Pulse(120 per min)
Bongs