Operating and display elements
2.2 Operating and display elements: CPU 31x
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
2-13
2.2.5 Status and error displays of CPU 31x
General status and error displays
Table 2-7 General status and error displays of the CPU 31x
LED designation Color Meaning
SF red Hardware or software error.
DC5 V green 5-V power for the CPU and the S7-300 bus
FRCE yellow LED is lit: Active force job
LED flashes at 2 Hz: Node flash test function (only CPUs with
firmware V2.2.0 or higher)
RUN green CPU in RUN
The LED flashes during STARTUP at a rate of 2 Hz, and in HOLD
state at 0.5 Hz.
STOP yellow CPU in STOP, or HOLD, or STARTUP
The LED flashes at 0.5 Hz when the CPU requests a memory reset,
and during the reset at 2 Hz.
Status displays for the interfaces X1, X2 and X3
Table 2-8 Bus error displays of CPU 31x
CPU LED designation Color Meaning
315-2 DP BF red Bus error at DP interface (X2)
BF1: red Bus error at interface 1 (X1) 317-2 DP
BF2: red Bus error at interface 2 (X2)
BF1: red Bus error at interface 1 (X1)
BF2: red Bus error at interface 2 (X2)
LINK green Connection at interface 2 (X2) is active
31x-2 PN/DP
RX/TX yellow Receive / Transmit data at interface 2 (X2)
BF1: red Bus error at interface 1 (X1)
BF2: red Bus error at interface 2 (X2)
BF3: red Bus error at interface 3 (X3)
LINK
1
green Connection at interface 3 (X3) is active
319-3 PN/DP
RX/TX
1
yellow Receive / transmit data at interface 3 (X3)
1
In the case of the CPU 319-3 PN/DP are located directly at the RJ45 socket (LEDs are not
labeled!)

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g