EasyManuals Logo

Siemens CPU 313C User Manual

Siemens CPU 313C
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Communication
3.2 Communication services
CPU 31xC and CPU 31x, Technical Data
Manual, 01/2006 Edition, A5E00105475-06
3-7
Communication service Functionality Time at which the S7
connection is established ...
via MPI via DP via
PtP
via
PN
PROFINET IO Data exchange between IO
controllers and the IO
devices
does not require an S7
connection
X
SNMP
(Simple Network
Management Protocol)
Standard protocol for
network diagnostics and
configuration
does not require an S7
connection
X
open communication by
means of TCP/IP
Data exchange via
Industrial Ethernet with
TCP/IP protocol (by means
of loadable FBs)
Does not require an S7
connection, is handled in the
user program by means of
loadable FBs
X
Open communication by
means of ISO on TCP
Data exchange via
Industrial Ethernet with
ISO-on-TCP protocol (by
means of loadable FBs)
Does not require an S7
connection, is handled in the
user program by means of
loadable FBs
X
Open communication by
means of UDP
Data exchange via
Industrial Ethernet with
UDP protocol (by means of
loadable FBs)
Does not require an S7
connection, is handled in the
user program by means of
loadable FBs
X
See also
Distribution and availability of S7 connection resources (Page 3-30)
Connection resources for routing (Page 3-32)
3.2.2 PG communication
Properties
PG communication is used to exchange data between engineering stations (PG, PC, for
example) and SIMATIC modules which are capable of communication. This service is
available for MPI, PROFIBUS and Industrial Ethernet subnets. Transition between subnets is
also supported.
PG communication provides the functions needed to download / upload programs and
configuration data, to run tests and to evaluate diagnostic information. These functions are
integrated in the operating system of
SIMATIC S7 modules.
A CPU can maintain several simultaneous online connections to one or multiple PGs.

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g