3.2 Communication services
CPU 31xC and CPU 31x, Technical Data
3-10 Manual, 01/2006 Edition, A5E00105475-06
Send and receive conditions
Conditions which should be satisfied for GD communication:
For the transmitter of a GD packet:
Reduction ratio
transmitter
x cycle time
transmitter
≥ 60 ms
For the receiver of a GD packet:
Reduction ratio
receiver
x cycle time
receiver
< reduction ratio
transmitter
x cycle time
transmitter
A GD packet may be lost if you do not adhere to these conditions. The reasons being:
the performance of the "smallest" CPU in the GD circuit
asynchronous transmitting / receiving of global data at the stations
When setting in STEP 7: “Transmit after each CPU cycle“, and the CPU has a short scan
cycle time (< 60 ms), the operating system might overwrite a GD packet of the CPU before it
is transmitted. The loss of global data is indicated in the status box of a GD circuit, if you set
this function in your STEP 7 configuration.
GD resources of the CPUs
Table 3-4 GD resources of the CPUs
Parameters CPU 31xC, 312, 314 CPU 315-2 DP, 315-2 PN/DP,
317-2 DP, 317-2 PN/DP,
319-3 PN/DP
Number of GD circuits per CPU Max. 4 Max. 8
GD packets transmitted per GD circuit Max. 1 Max. 1
GD packets transmitted by all GD circuits Max. 4 Max. 8
GD packets received per GD circuit Max. 1 Max. 1
GD packets received by all GD circuits Max. 4 Max. 8
Data length per GD packet Max. 22 bytes Max. 22 bytes
Consistency Max. 22 bytes Max. 22 bytes
Min. reduction ratio (default) 1 (8) 1 (8)

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g