EasyManuals Logo

Siemens CPU 313C User Manual

Siemens CPU 313C
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #88 background imageLoading...
Page #88 background image
Cycle and reaction times
5.2 Cycle time
CPU 31xC and CPU 31x, Technical Data
5-2 Manual, 01/2006 Edition, A5E00105475-06
Meaning of the term cycle time
The cycle time represents the time that an operating system needs to execute a program,
that is, one OB 1 cycle, including all program sections and system activities interrupting this
cycle. This time is monitored.
Time slice model
Cyclic program processing, and therefore user program execution, is based on time shares.
To clarify these processes, let us assume that every time share has a length of precisely
1 ms.
Process image
During cyclic program processing, the CPU requires a consistent image of the process
signals. To ensure this, the process signals are read/written prior to program execution.
Subsequently, the CPU does not address input (I) and output (Q) address areas directly at
the signal modules, but rather accesses the system memory area containing the I/O process
image.
Sequence of cyclic program processing
The table and figure below show the phases in cyclic program processing.
Table 5-1 Cyclic program processing
Step Sequence
1 The operating system initiates cycle time monitoring.
2 The CPU copies the values of the process image of outputs to the output modules.
3 The CPU reads the status at the inputs of the input modules and then updates the
process image of inputs.
4 The CPU processes the user program in time shares and executes program instructions.
5 At the end of a cycle, the operating system executes queued tasks, for example, loading
and deleting blocks.
6 The CPU then returns to the start of the cycle, and restarts cycle time monitoring.

Table of Contents

Other manuals for Siemens CPU 313C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 313C and is the answer not in the manual?

Siemens CPU 313C Specifications

General IconGeneral
MPI InterfaceYes
Number of digital inputs24
Number of digital outputs16
Number of analog inputs4
Number of analog outputs2
Supply voltage24 V DC
High-speed countersYes
Bit Operations Execution Time0.1 µs
Word Operations Execution Time0.2 µs
Power Consumption5 W
Dimensions (W x H x D)40 x 125 x 130 mm
Operating Temperature0 to 60 °C
Communication InterfacesMPI
Programming LanguagesLAD, FBD, STL
Product type designationCPU 313C
Weight490 g