EasyManua.ls Logo

Siemens ET 200S - Page 160

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Diagnostics
6-36
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Module Status
The module status for the ET 200S with the IM151-1 BASIC is structured as
follows:
Byte 9
Byte 10
70
Byte 11
70
82
H
0
H
0
H
76 54 132 0
Byte 13
Byte 12
Bit no.
Modules 1 to 4
Byte 14
Modules 5 to 8
Byte 15
Modules 9 to 12
00
B
: Module OK; valid user data
01
B
: Module error; invalid user data
10
B
: Incorrect module; invalid user data
11
B
: No module (or module failure); invalid user data
Status
type:
Module
status
Not
applicable
Not
applicable
70
Bit no.
Code for module status
00
56
Length of the module status
including byte 15 (= 7 bytes)
11
1
0
0
0
1234
Figure 6-23 Structure of the Module Status for the ET 200S with the IM151-1 BASIC

Table of Contents

Related product manuals