Commissioning and Diagnostics
6-35
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
The module diagnosis for the ET 200S with the IM151-1 STANDARD, IM151-1 FO
STANDARD, and IM151-1 HIGH FEATURE is structured as follows:
Byte 6
Bit no.
Byte 7
Byte 8
713654
2
0
Byte 9
Byte 10
Byte 11
Byte 12
Byte 13
Byte 14
Module: 1 to 8
Module: 9 to 16
Module: 17 to 24
Module: 25 to 32
Module: 33 to 40
Module: 41 to 48
Module: 49 to 56
Module: 57 to 63
7
1365
42
8
16 15 1314 1112 10 9
18
1920
23
22 21 17
28
24
36
2729303132
34
35
26 25
39
40 3738
47
33
414648
4950
4345
44
42
53 525456 55
61
51
58
62 59
60
5763
Events on the correspon-
ding module are indica-
ted by set bits.
70
Bit no.
Length of the module diagnosis
including byte 6 (= 9 bytes)
Code for module diagnosis
01
65
100100
* Always 0
*
Figure 6-22 Structure of the Module Diagnosis for the ET 200S with the IM151-1
STANDARD, IM151-1 FO STANDARD, and IM151-1 HIGH FEATURE
6.6.7 Module Status
Definition
The module status indicates the status of the configured modules and expands on
the module diagnosis as regards the configuration. The module status begins after
the module diagnosis and comprises:
7 bytes in the case of the IM151-1 BASIC
20 bytes in the case of the IM151-1 STANDARD IM151-1 FO STANDARD, and
IM151-1 HIGH FEATURE