EasyManua.ls Logo

Siemens ET 200S - Page 164

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning and Diagnostics
6-40
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
The channel-specific diagnosis for the ET200S with the IM151-1 STANDARD,
IM151-1 FO STANDARD, and IM151-1 HIGH FEATURE is structured as follows:
7
Bit no.
10
654 132
000000
B
to 111111
B
: Slot of the module that supplies the
channel-specific diagnosis.
0
7
Bit no.
654 132
0
Byte 36
000000
B
to 000011
B
: Number of the channel that supplies the diagnosis
7
Bit no.
654 132
0
Byte 37
Error type (see Table 6-12 to Table 6-22)
Channel
type:
Byte 35
001
B
: Bit
010
B
: 2 bits
011
B
: 4 bits
100
B
: Byte
101
B
: Word
110
B
: 2 words
01
B
: Input channel
10
B
: Output channel
11
B
: Input/output channel
Bytes 38
to 40
Next channel-specific diagnostic message
(assignment as for bytes 35 to 37)
Max. byte 63
Code for channel-specific diagnosis
..
In DPV0 operation: IM151-1, IM151-1 FO STANDARD, IM151-1
HIGH FEATURE
Max. byte 127
In DPV1 operation: IM151-1 HIGH FEATURE
Figure 6-26 Structure of the Channel-Specific Diagnosis for the ET 200S with the IM151-1
STANDARD, IM151-1 FO STANDARD, and IM151-1 HIGH FEATURE
Note
The slot of the module is coded in bits 0 to 5 of byte 16/35. The following applies:
displayed number +1 ¢ slot of the module (0 ¢ slot 1; 1 ¢ slot 2; 3 ¢ slot 4,
etc.)
In bits 6/7 of byte 17/36, 00
B
is output if a power module reports a channel-specific
diagnosis.