Commissioning and Diagnostics
6-41
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Power Module Error Types
The diagnostic message is reported on channel 0 and applies to the whole module.
Table 6-12 Power Module Error Types
Power Modules Electronic
Modules
Error Type Meaning What to Do
PM-E
24–48 VDC/
120–230 VAC
PM-E
24 VDC
17
D
10001: Sensor or load
voltage missing
No supply voltage,
or inadequate
supply voltage.
Correct the process
wiring. Check the
supply voltage.
––– 18
D
10010: Fuse defect The fuse in the
power module has
tripped.
Replace the fuse.
Digital Electronic Module Error Types
Table 6-13 Digital Electronic Module Error Types
Digital Electronic
Modules
Error Type Meaning What to Do
2DI 24 VDC High Feature 1
D
00001: Short circuit Short circuit of the
sensor supply. The
diagnostic
message is issued
on channel 0 and
applies to the
whole module.
Correct the process
wiring (sensor
wiring).
4DI 24 VDC High Feature 1
D
00001: Short circuit
(In connection with
IM151-1 BASIC /
IM151-1 STANDARD, as
of
6ES7 151-1AA02-0AB0,
IM151-1 FO
STANDARD, as of
6ES7 151-1AB01-0AB0)
or IM151-1 HIGH
FEATURE
Short circuit of the
sensor supply. The
diagnostic
message is issued
on channel 0 and
applies to the
whole module.
Correct the process
wiring (sensor
wiring).
26
D
11010: External fault
(In connection with
IM151-1 STANDARD, up
to
6ES7 151-1AA01-0AB0
or IM151-1 FO
STANDARD, up to
6ES7 151-1AB00-0AB0)