Interface Modules
8-3
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 8-3 Parameters for the IM151-1 HIGH FEATURE Interface Module (Parameter
Assignment Tab)
IM151-1 HIGH
FEATURE
ApplicabilityDefaultValue Range
Insert/remove-module
interrupt
1
Disable/enable Disable ET 200S
Identifier-related
diagnostics
Disable/enable Enable ET 200S
Module status Disable/enable Enable ET 200S
Channel-specific
diagnosis
Disable/enable Enable ET 200S
Analog-value format SIMATIC S7/
SIMATIC S5
S7 ET 200S
Interference
frequency
suppression
50 Hz/ 60 Hz 50 Hz ET 200S
Reference junction
slot
None/2 to 63 None ET 200S
Reference junction
input
RTD on channel 0/
RTD on channel 1
0 ET 200S
1
In the device database file, the default setting of the parameter is ”Enable”.
2
Only parameterizable in DPV1 operation of the IM151-1 HIGH FEATURE.
Table 8-4 Parameters for the IM151-1 HIGH FEATURE Interface Module (Clocking Tab)
IM151-1 HIGH
FEATURE
Value Range Default Applicability
Synchronize DP
slave with DP cycle
1
Disable/enable Disable ET 200S
Time Ti (read in
process values)
1
(Values are preset by
STEP 7)
(Value is preset by
STEP 7)
ET 200S
Time To (read out
process values)
1
(Values are preset by
STEP 7)
(Value is preset by
STEP 7)
ET 200S
1
Only parameterizable as of STEP7 V5.1 with ServicePack 3
DPV1 Operation (only with IM151-1 HIGH FEATURE)
This parameter allows you to enable or disable DPV1 operation of the ET 200S. If
DPV1 operation is enabled, C1 data records and interrupts are supported
(parameterizable).
Prerequisite:
The DP master also support DPV1.