Interface Modules
8-16
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
8.5 IM151-1 HIGH FEATURE Interface Module
(6ES7 151-1BA00-0AB0)
Order Number
6ES7 151-1BA00-0AB0
Features
The IM151-1 HIGH FEATURE interface module has the following features:
It connects the ET 200S with PROFIBUS-DP.
It prepares the data for the electronic modules and motor starters that are fitted.
It supplies the backplane bus.
It can be synchronized with the DP cycle (clocking).
The firmware can be updated via PROFIBUS-DP using HWCONFIG.
The PROFIBUS-DP address of the ET 200S can be set by means of switches.
If the 24 VDC power supply is disconnected, the IM151-1 HIGH FEATURE
interface module is also disconnected.
The maximum address space is 244 bytes for inputs and 244 bytes for outputs.
The reference potential M of the rated supply voltage of the IM151-1 HIGH
FEATURE to the rail (protective conductor) is connected by means of an RC
combination, thus permitting an ungrounded configuration.
It can be operated as a DPV0 slave.
Acyclic data exchange (read/write data record): class 2 services (e.g.
updating firmware)
It can be operated as a DPV1 slave.
Acyclic data exchange (read/write data record): class 2 services (e.g.
updating firmware) and class 1 services
Diagnostic interrupts
Hardware interrupts
Insert/remove-module interrupts
A maximum of 63 modules can be operated with the IM151-1 HIGH FEATURE.
The maximum width of the station is 1 m.