Digital Electronic Modules
11-67
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Technical Specifications
Dimensions and Weight
Dimensions W H D
(mm)
15 81 52
Weight Approx. 37 g
Data for Specific Modules
Number of outputs 2
Length of cable
Unshielded Max. 600 m
Shielded Max. 1000 m
Voltage, Currents, Potentials
Rated load voltage L1 (from
the power module)
24-230 VAC
Frequency 47 to 63 Hz
Total current of the outputs
(per module)
Up to 40 °C Max. 2 A
Up to 60 °C Max. 1 A
Isolation
Between the channels No
Between the channels
and backplane bus
Yes
Insulation tested 4000 VDC
Current consumption
From the backplane bus Max. 18 mA
From rated load voltage
L1 (no load)
Max. 15 mA per
channel
Power dissipation of the
module
Max. 4 W
Status, Interrupts, Diagnostics
Status display Green LED per
Channel
Diagnostic functions No
Data for Selecting an Actuator
Output voltage
At signal “1” Min. L (-1.5 V)
Output current
At signal “1”
– Rated value
– Permitted Range
1 A
0.1 mA to 2.2 A
With signal “0” (leakage
current)
Max. 3 mA
Output delay (for resistive
load)
At “0” to “1” Max. 15 ms
At “1” to “0” Max. 15 ms
Zero cross inhibit voltage Max. 25 V
Motor starter size
Up to 40 °C Max. size in
accordance with
NEMA: 5
Up to 60 °C Max. size in
accordance with
NEMA: 4
Lamp load Max. 100 W
Connecting two outputs in
parallel
For redundant triggering
of a load
Yes (per module)
To increase
performance
No
Control of a digital input Possible
Switch rate
For resistive load Max. 10 Hz
With inductive load Max. 0.5 Hz
For lamp load Max. 1 Hz
Short-circuit protection of
the output
Yes, by means of
fuse in the power
module