Digital Electronic Modules
11-74
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 11-19 Switching Capacity and Lifetime of the Relay Contacts
Resistive Load Operating Cycles
(Typical)
CurrentVoltage
For inductive load in 230 VAC 2.0 A 0.1 million
accordance with
IEC 947-5-1 DC 13/
1.0 A 0.3 million
IEC 947-5-1 DC 13/
AC 15
0.5 A 1 million
11.18 2RO NO/NC 2448 VDC/5 A,
24230 VAC/5 A Digital Electronic Module
(6ES7 132-4HB10-0AB0)
Note
If you connect an extra-low voltage system (SELV/ PELV) on one channel of the
relay module, you can only use an extra-low voltage system (SELV/ PELV) on the
other channel.
Features
Digital electronic module with two relay outputs
Output current 5 A per output
Substitute value
Parameter assignment length: 3 bytes
Suitable for solenoid valves, DC contactors, and indicator lights
Isolated from the supply voltage
Normally open contact and normally closed contact
!
Caution
The rated supply voltage of the 2RO NO/NC 2448 VDC/5 A, 24230 VAC/5 A is
24 VDC. The 2RO NO/NC 2448 VDC/5 A, 24230 VAC/5 A can only be located
in a potential group with 24 VDC (from the power module).

Table of Contents

Related product manuals