Digital Electronic Modules
11-75
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Terminal Assignment
The following table indicates the terminal assignment of the 2RO NO/NC
24–48 VDC/5 A, 24–230 VAC/5 A for the different terminal modules:
Table 11-20 Terminal Assignment of the 2RO NO/NC 24–48 VDC/5 A, 24–230 VAC/5 A
View
Terminal Assignment Remarks
Normally open
contact
AUX1 (e.g. PE)
2
3
4
6
7
8
1
5
AUX1 (e.g. PE)
TM-E15S24-A1 and 2RO NO/NC
24–48 VDC/5 A, 24–230 VAC/5 A
CH1CH0
The AUX1 bus must
be applied to PE.
Common
Normally clo-
sed contact
Common
Normally open
contact
Normally closed
contact
AA
]
]
Channel 0:
Terminals 1 to 3
Channel 1:
Terminals 5 to 7
1, 2: normally open
contact channel 0
1, 3: normally closed
contact channel 0
5, 6: normally open
contact channel 1
5, 7: normally closed
contact channel 1
2
3
4
6
7
8
1
5
TM-E15S24-01 and 2RO NO/NC
24–48 VDC/5 A, 24–230 VAC/5 A
CH1CH0
Common
Normally
open contact
Normally closed
contact
Common
Normally
open contact
Normally
closed contact
]
Channel 0:
Terminals 1 to 3
Channel 1:
Terminals 5 to 7
1, 2: normally open
contact channel 0
1, 3: normally closed
contact channel 0
5, 6: normally open
contact channel 1
5, 7: normally closed
contact channel 1