Digital Electronic Modules
11-80
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 11-21 Switching Capacity and Lifetime of the Contacts
Resistive Load Operating
Cycles (typ.)
Normally Closed
Contact
Operating
Cycles (typ.)
Normally Open
Contact
CurrentVoltage
For inductive load 24 VDC 2.0 A 0.1 million 0.1 million
in accordance with
IEC 947-5-1 DC
1.0 A 0.2 million 0.2 million
IEC 947-5-1 DC
13/ AC15
0.5 A 0.5 million 0.5 million
48 VDC 2.0 A 0.07 million 0.05 million
1.0 A 0.15 million 0.1 million
0.5 A 0.4 million 0.25 million
48 VAC 1.0 A 0.5 million 0.3 million
60 VAC 1.0 A 0.5 million 0.3 million
120 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.3 million 0.1 million
0.5 A 0.9 million 0.6 million
0.1 A 1.5 million 1.0 million
230 VAC 2.0 A 0.1 million 0.1 million
1.0 A 0.5 million 0.3 million
0.5 A 0.9 million 0.6 million
0.1 A 1.0 million 1.0 million