EasyManua.ls Logo

Siemens ET 200S - Page 363

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-7
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 12-3 Measured-Value Resolution of the Analog Values (SIMATIC S7 Format)
Units Analog Value
Resolution in Bits
Decimal Hexadec. High byte Low byte
11+ sign (S) 16 10
H
S 0 0 0 0 0 0 0 0 0 0 1 x x x x
12 + sign (S) 8 8
H
S 0 0 0 0 0 0 0 0 0 0 0 1 x x x
13 + sign (S) 4 4
H
S 0 0 0 0 0 0 0 0 0 0 0 0 1 x x
15 + sign (S) 1 1
H
S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
Note: This resolution does not apply to temperature values. The converted
temperature values are the result of a conversion in the analog electronic module
(see Table 12-3).
Note
The following applies to temperature measurements: In the overrange and
underrange, the gradient of the characteristic curve at the point where the
linearized rated range is left is retained.