Analog Electronic Modules
12-9
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Ranges for Voltage and Current: 1 to 5 V, 0 to 20 mA, 4 to 20 mA
Table 12-5 SIMATIC S7 Format: Measuring Ranges 1 to 5 V, 0 to 20 mA, 4 to 20 mA
Measuring
Measuring Measuring Units
Range
1 to 5 V
Range
0 to 20 mA
Range
4 to 20 mA
Decimal Hexadec.
Range
> 5.704 > 23.5178 > 22.8142 32767 7FFF
H
Overflow
5.704 23.5178 22.8142 32511 7EFF
H
: : : : :
Overrange
5.000145 20.0007 20.0005 27649 6C01
H
5.000 20.0000 20.0000 27648 6C00
H
3.000 16.0000 16.0000 20736 5100
H
: : : : : Rated range
1.000 0.0000 4.0000 0 0
H
0.999855 3.9995 1 FFFF
H
:
Negative
: :
Underrange
0.296
values not
possible
1.1852 4864 ED00
H
< 0.296
possible
< 1.1852 32768 8000
H
Underflow
Measuring Range for Current: " 20 mA
Table 12-6 SIMATIC S7 Format: Measuring Range "20 mA
Measuring range
"
Units
" 20 mA
Decimal Hexadecimal
Range
> 23.5150 32767 7FFF
H
Overflow
23.5150 32511 7EFF
H
: : :
Overrange
20.0007 27649 6C01
H
20.0000 27648 6C00
H
14.9980 20736 5100
H
: : : Rated range
14.9980 20736 AF00
H
20.0000 27648 9400
H
20.0007 27649 93FF
H
: : :
Underrange
23.5160 32512 8100
H
< 23.5160 32768 8000
H
Underflow