Analog Electronic Modules
12-11
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Ranges for Resistance Thermometer Pt x00 Standard
Table 12-8 SIMATIC S7 Format: Measuring Ranges Pt 100, 200, 500, 1000 Standard in °C and °F
Pt x00
Standard
5
Units Pt x00
Standard
5
Units
in
C
(1 digit =
0.15C)
Dec. Hex.
in
F
(1 digit =
0.1 5F)
Dec. Hex.
Range
> 1000.0 32767 7FFF
H
> 1832.0 32767 7FFF
H
Overflow
1000.0
:
850.1
10000
:
8501
2710
H
:
2135
H
1832.0
:
1562.1
18320
:
15621
4790
H
:
3D05
H
Overrange
850.0
:
–200.0
8500
:
–2000
2134
H
:
F830
H
1562.0
:
–328.0
15620
:
–3280
3D04
H
:
F330
H
Rated range
–200.1
:
–243.0
–2001
:
–2430
F82F
H
:
F682
H
–328.1
:
–405.4
–3281
:
–4054
F32F
H
:
F02A
H
Underrange
< – 243.0 –32768 8000
H
< – 405.4 –32768 8000
H
Underflow
Measuring Ranges for Resistance Thermometer Pt x00 Climatic
Table 12-9 SIMATIC S7 Format: Measuring Ranges Pt 100, 200, 500, 1000 Climatic in °C and °F
Pt x00
Climatic
5
Units Pt x00
Climatic
5
Units
in
C
(1 digit =
0.015C)
Dec. Hex.
in
F
(1 digit =
0.01 5F)
Dec. Hex.
Range
> 155.00 32767 7FFF
H
> 311.00 32767 7FFF
H
Overflow
155.00
:
130.01
15500
:
13001
3C8C
H
:
32C9
H
311.00
:
266.01
31100
:
26601
797C
H
:
67E9
H
Overrange
130.00
:
–120.00
13000
:
–12000
32C8
H
:
D120
H
266.00
:
–184.00
26600
:
–18400
67E8
H
:
B820
H
Rated range
–120.01
:
–145.00
–12001
:
–14500
D11F
H
:
C75C
H
–184.01
:
–229.00
–18401
:
–22900
B81F
H
:
A68C
H
Underrange
< – 145.00 –32768 8000
H
< – 229.00 –32768 8000
H
Underflow