Analog Electronic Modules
12-12
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Ranges for Resistance Thermometer Ni x00 Standard
Table 12-10SIMATIC S7 Format: Measuring Ranges Ni 100, 120, 200, 500, 1000 Standard in °C and °F
Ni x00
Standard
5
Units Ni x00
Standard
5
Units
in
C
(1 digit =
0.15C)
Dec. Hex.
in
C
(1 digit =
0.15F)
Dec. Hex.
Range
> 295.0 32767 7FFF
H
> 563.0 32767 7FFF
H
Overflow
295.0 2950 B86
H
563.0 5630 15FE
H
: : : : : :
Overrange
250.1 2501 9C5
H
482.1 4821 12D5
H
250.0 2500 9C4
H
482.0 4820 12D4
H
: : : : : : Rated range
–60.0 –600 FDA8
H
–76.0 –760 FD08
H
–60.1 –601 FDA7
H
–76.1 –761 FD07
H
: : : : : :
Underrange
–105.0 –1050 FBE6
H
–157.0 –1570 F9DE
H
< –105.0 –32768 8000
H
< –157.0 –32768 8000
H
Underflow
Measuring Ranges for Resistance Thermometer Ni x00 Climatic
Table 12-11 SIMATIC S7 Format: Measuring Ranges Ni 100, 120, 200, 500, 1000 Climatic in °C and °F
Ni x00
Climatic
5
Units Ni x00
Climatic
5
Units
in
C
(1 digit =
0.015C)
Dec. Hex.
in
F
(1 digit =
0.01 5F)
Dec. Hex.
Range
> 295.00 32767 7FFF
H
> 325.11 32767 7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overrange
250.00
:
–60.00
25000
:
–6000
61A8
H
:
E890
H
280.00
:
–76.00
28000
:
–7600
6D60
H
:
E250
H
Rated range
–60.01
:
–105.00
–6001
:
–10500
E88F
H
:
D6FC
H
–76.01
:
–157.00
–7601
:
–15700
E24F
H
:
C2AC
H
Underrange
< – 105.00 –32768 8000
H
< – 157.00 –32768 8000