Analog Electronic Modules
12-15
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple Type E
Table 12-16SIMATIC S7 Format: Measuring Range Type E in °C and °F
Units Units
Type E
in 5C
Dec. Hex.
Type E
in 5F
Dec. Hex.
Range
> 1200.0 32767 7FFF
H
> 2192.0 32767 7FFF
H
Overflow
1200.0
:
1000.1
12000
:
10001
2EE0
H
:
2711
H
2192.0
:
1832.1
21920
:
18321
55A0
H
:
4791
H
Overrange
1000.0
:
270.0
10000
:
2700
2710
H
:
F574
H
1832.0
:
454.0
18320
:
4540
4790
H
:
EE44
H
Rated range
< 270.0 32768 8000
H
< 454.0 32768 8000
H
Underflow
Measuring Range for Thermocouple Type J
Table 12-17SIMATIC S7 Format: Measuring Range Type J in °C and °F
Units Units
Type J
in 5C
Dec. Hex.
Type J
in 5F
Dec. Hex.
Range
> 1450.0 32767 7FFF
H
> 2642.0 32767 7FFF
H
Overflow
1450.0
:
1200.1
14500
:
12010
38A4
H
:
2EEA
H
2642.0
:
2192.1
26420
:
21921
6734
H
:
55A1
H
Overrange
1200.0
:
210.0
12000
:
2100
2EE0
H
:
F7CC
H
2192.0
:
346.0
21920
:
3460
55A0
H
:
F27C
H
Rated range
< 210.0 32768 8000
H
< 346.0 32768 8000
H
Underflow