Analog Electronic Modules
12-16
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple Type K
Table 12-18SIMATIC S7 Format: Measuring Range Type K in °C and °F
Units Units
Type K
in 5C
Dec. Hex.
Type K
in 5F
Dec. Hex.
Range
> 1622.0 32767 7FFF
H
> 2951.6 32767 7FFF
H
Overflow
1622.0
:
1372.1
16220
:
13721
3F5C
H
:
3599
H
2951.6
:
2501.7
29516
:
25062
734C
H
:
61B9
H
Overrange
1372.0
:
270.0
13720
:
2700
3598
H
:
F574
H
2501.6
:
454.0
25061
:
4540
61B8
H
:
EE44
H
Rated range
< 270.0 32768 8000
H
< 454.0 32768 8000
H
Underflow
Measuring Range for Thermocouple Type L
Table 12-19SIMATIC S7 Format: Measuring Range Type L in °C and °F
Units Units
Type L
in 5C
Dec. Hex.
Type L
in 5F
Dec. Hex.
Range
> 1150.0 32767 7FFF
H
> 2102.0 32767 7FFF
H
Overflow
1150.0
:
900.1
11500
:
9001
2CEC
H
:
2329
H
2102.0
:
1652.1
21020
:
16521
521C
H
:
4089
H
Overrange
900.0
:
200.0
9000
:
2000
2328
H
:
F830
H
1652.0
:
328.0
16520
:
3280
4088
H
:
F330
H
Rated range
< 200.0 32768 8000
H
< 328.0 32768 80000
H
Underflow