Analog Electronic Modules
12-27
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Resistance Thermometer: Ni x00 Standard
Table 12-37SIMATIC S5 Format: Measuring Range Ni 100, 120, 200, 500, 1000 Standard in C
Measured
Value
_
Units
(Deci-
Data Word Range
in
C
(1 digit =
0.5_C)
mal)
12 11109 8 7 6543210XEO
> 295 591 0 0 0 1 0 0 1 0 0 1 1 1 1 0 0 1 Overflow
295 590 0 0 0 1 0 0 1 0 0 1 1 1 0 0 0 0 Overrange
250.5 501 0 0 0 0 1 1 1 1 1 0 1 0 1 0 0 0
250 500 0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 Rated
0.5 1 0 0 0 0 0 0 0000001000
range
0 0 0 0 0 0 0 0 0000000000
–0.5 –1 1 1 1 1 1 1 1111111000
–60 –120 1 1 1 1 1 1 0001000000
–60.5 –121 1 1 1 1 1 1 1 1 0 0 0 0 1 0 0 0 Underrange
–105 –210 1 1 1 1 1 0 0 1 0 1 1 1 0 0 0 0
< –105 –211 1 1 1 1 1 0 0 1 0 1 1 0 1 0 0 1 Underflow
Table 12-38SIMATIC S5 Format: Measuring Range Ni 100, 120, 200, 500, 1000 Standard in F
Measured
Value
_
Units
(Deci-
Data Word Range
in
F
(1 digit =
0.5_F)
mal)
12 11109 8 7 6543210XEO
> 563 1127 0 0 1 0 0 0 1 1 0 0 1 1 1 0 0 1 Overflow
563 1126 0 0 1 0 0 0 1 1 0 0 1 1 0 0 0 0 Overrange
482.5 965 0 0 0 0 1 1 1 1 0 0 0 0 1 0 0 0
482 964 0 0 0 1 1 1 1 0 0 0 1 0 0 0 0 0 Rated
0.5 1 0 0 0 0 0 0 0000001000
range
0 0 0 0 0 0 0 0 0000000000
–0.5 –1 1 1 1 1 1 1 1111111000
–76 –152 1 1 1 1 1 0 1101000000
–76.5 –153 1 1 1 1 1 0 1 1 0 0 1 1 1 0 0 0 Underrange
–157 –314 1 1 1 1 0 1 1 0 0 0 1 1 0 0 0 0
< –157 –315 1 1 1 1 0 1 1 0 0 0 1 0 1 0 0 1 Underflow