Analog Electronic Modules
12-28
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Resistance Thermometer: Ni x00 Climatic
Table 12-39SIMATIC S5 Format: Measuring Range Ni 100, 120, 200, 500, 1000 Climatic in C
Measured
Value
_
Units
(Deci-
Data Word Range
in
C
(1 digit =
0.1_C)
mal)
12 11109 8 7 6543210XEO
> 295 2951 0 1 0 1 1 1 0 0 0 0 1 1 1 0 0 1 Overflow
295 2950 0 1 0 1 1 1 0 0 0 0 1 1 0 0 0 0 Overrange
250.1 2501 0 1 0 0 1 1 1 0 0 0 1 0 1 0 0 0
250 2500 0 1 0 0 1 1 1 0 0 0 1 0 0 0 0 0 Rated
0.1 1 0 0 0 0 0 0 0000001000
range
0 0 0 0 0 0 0 0 0000000000
–0.1 –1 1 1 1 1 1 1 1111111000
–60 –600 1 1 1 0 1 1 0101000000
–60.1 –601 1 1 1 0 1 1 0 1 0 0 1 1 1 0 0 0 Underrange
–105 –1050 1 1 0 1 1 1 1 1 0 0 1 1 0 0 0 0
< –105 –1051 1 1 0 1 1 1 1 1 0 0 1 0 1 0 0 1 Underflow
Table 12-40SIMATIC S5 Format: Measuring Range Ni 100, 120, 200, 500, 1000 Climatic in F
Measured
Value
_
Units
(Deci-
Data Word Range
in
F
(1 digit =
0.2_F)
mal)
12 11109 8 7 6543210XEO
> 563 2816 0 1 0 1 1 0 0 0 0 0 0 0 0 0 0 1 Overflow
563 2815 0 1 0 1 0 1 1 1 1 1 1 1 0 0 0 0 Overrange
482.2 2411 0 1 0 0 1 0 1 1 0 1 0 1 1 0 0 0
482 2410 0 1 0 0 1 0 1 1 0 1 0 1 0 0 0 0 Rated
0.2 1 0 0 0 0 0 0 0000001000
range
0.0 0 0 0 0 0 0 0 0000000000
–0.2 –1 1 1 1 1 1 1 1111111000
–76 –380 1 1 1 1 0 1 0000100000
–76.2 –381 1 1 1 1 0 1 0 0 0 0 0 1 1 0 0 0 Underrange
–157 –785 1 1 1 0 0 1 1 1 0 1 1 1 1 0 0 0
< –157 –786 1 1 1 0 0 1 1 1 0 1 1 1 0 0 0 1 Underflow