Analog Electronic Modules
12-29
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Resistance Thermometer: Cu 10 Standard
Table 12-41SIMATIC S5 Format: Measuring Range Cu 10 Standard in C
Measured
Value
Units
(Deci-
Data Word Range
in
C
(1 digit =
0.5_C)
mal)
12 11109 8 7 6543210XEO
> 312 625 0 0 0 1 0 0 1 1 1 0 0 0 1 0 0 1 Overflow
312 624 0 0 0 1 0 0 1 1 1 0 0 0 0 0 0 0 Overrange
260.5 521 0 0 0 1 0 0 0 0 0 1 0 0 1 0 0 0
260 520 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 Rated
0.5 1 0 0 0 0 0 0 0000001000
range
0 0 0 0 0 0 0 0 0000000000
–0.5 –1 1 1 1 1 1 1 1111111000
–200 –400 1 1 1 1 0 0 1110000000
–200.5 –401 1 1 1 1 0 0 1 1 0 1 1 1 1 0 0 0 Underrange
–240 –480 1 1 1 1 0 0 0 1 0 0 0 0 0 0 0 0
< –240 –481 1 1 1 1 0 0 0 0 1 1 1 1 1 0 0 1 Underflow
Table 12-42SIMATIC S5 Format: Measuring Range Cu 10 Standard in F
Measured
Value
_
Units
(Deci-
Data Word Range
in
F
(1 digit =
0.5_F)
mal)
12 11109 8 7 6543210XEO
> 594.0 1189 0 0 1 0 0 1 0 1 0 0 1 0 1 0 0 1 Overflow
594.0 1188 0 0 1 0 0 1 0 1 0 0 1 0 0 0 0 0 Overrange
500.5 1001 0 0 0 1 1 1 1 1 0 1 0 0 1 0 0 0
500 1000 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0 Rated
0.5 1 0 0 0 0 0 0 0000001000
range
0.0 0 0 0 0 0 0 0 0000000000
–0.5 –1 1 1 1 1 1 1 1111111000
–328 –656 1 1 1 0 1 0 1110000000
–328.5 –657 1 1 1 0 1 0 1 1 0 1 1 1 1 0 0 0 Underrange
–400 –800 1 1 1 0 0 1 1 1 0 0 0 0 0 0 0 0
<–400 –801 1 1 1 0 0 1 1 0 1 1 1 1 1 0 0 1 Underflow