Analog Electronic Modules
12-30
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Resistance Thermometer: Cu 10 Climatic
Table 12-43SIMATIC S5 Format: Measuring Range Cu 10 Climatic in C
Measured
Value
Units
(Deci-
Data Word Range
in
C
(1 digit =
0.05_C)
mal)
12 11109 8 7 6543210XEO
> 180 3601 0 1 1 1 0 0 0 0 1 0 0 0 1 0 0 1 Overflow
180 3600 0 1 1 1 0 0 0 0 1 0 0 0 0 0 0 0 Overrange
150.05 3001 0 1 0 1 1 1 0 1 1 1 0 0 1 0 0 0
150 3000 0 1 0 1 1 1 0 1 1 1 0 0 0 0 0 0 Rated
0.05 1 0 0 0 0 0 0 0000001000
range
0 0 0 0 0 0 0 0 0000000000
–0.05 –1 1 1 1 1 1 1 1111111000
–50 –1000 1 1 1 1 1 0 0000110000
–50.05 –1001 1 1 1 1 1 0 0 0 0 0 1 0 1 0 0 0 Underrange
–60 –1200 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0 0
< –60 –1201 1 1 1 1 0 1 1 0 1 0 0 1 1 0 0 1 Underflow
Table 12-44SIMATIC S5 Format: Measuring Range Cu 10 Climatic in F
Measured
Value
_
Units
(Deci-
Data Word Range
in
F
(1 digit =
0.1_F)
mal)
12 11109 8 7 6543210XEO
> 356.1 3561 0 1 1 0 1 1 1 1 0 1 0 0 1 0 0 1 Overflow
356.1 3560 0 1 1 0 1 1 1 1 0 1 0 0 0 0 0 0 Overrange
280.1 2801 0 1 0 1 0 1 1 1 1 0 0 0 1 0 0 0
280 2800 0 1 0 1 0 1 1 1 1 0 0 0 0 0 0 0 Rated
0.1 1 0 0 0 0 0 0 0000001000
range
0.0 0 0 0 0 0 0 0 0000000000
–0.1 –1 1 1 1 1 1 1 1111111000
–58 –580 1 1 1 0 1 1 0111100000
–58.1 –581 1 1 1 0 1 1 0 1 1 1 0 1 1 0 0 0 Underrange
–76 –760 1 1 1 0 1 0 0 0 0 1 0 0 0 0 0 0
< –76 –761 1 1 1 0 1 0 0 0 0 0 1 1 1 0 0 1 Underflow