Analog Electronic Modules
12-32
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple: Type C in _C
Table 12-47SIMATIC S5 Format: Measuring Range Type C in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109 876543210XEO
> 2500 2501 0 1 0 0 1 1 1 0 0 0 1 0 1 0 0 1 Overflow
2500 2500 0 1 0 0 1 1 1 0 0 0 1 0 0 0 0 0 Overrange
2321 2321 0 1 0 0 1 0 0 0 1 0 0 0 1 0 0 0
2320 2320 0 1 0 0 1 0 0 0 1 0 0 0 0 0 0 0
1 1 0 00000000000100 0 Rated range
0 0 0 000000000000000
–1 –1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 Underrange
–120 –120 1 1 1 1 1 1 0 0 0 1 0 0 0 0 0 0
< –120 –121 1 1 1 1 1 1 0 0 0 0 1 1 1 0 0 1 Underflow
Measuring Range for Thermocouple: Type C in _F
Table 12-48SIMATIC S5 Format: Measuring Range Type C in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109 876543210XEO
> 3277 3278 0 1 1 0 0 1 1 0 0 1 1 1 0 0 0 1 Overflow
3277 3277 0 1 1 0 0 1 1 0 0 1 1 0 1 0 0 0 Rated range
32 32 0 000000100000000
31 31 0 0 0 0 0 0 0 0 1 1 1 1 1 0 0 0 Underrange
–184 –184 1 1 1 1 1 0 1 0 0 1 0 0 0 0 0 0
< –184 –185 1 1 1 1 1 0 1 0 0 0 1 1 1 0 0 1 Underflow