Analog Electronic Modules
12-33
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple: Type E in _C
Table 12-49SIMATIC S5 Format: Measuring Range Type E in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109876543210XEO
> 1200 1201 0 0 1 0 0 1 0 1 1 0 0 0 1 0 0 1 Overflow
1200 1200 0 0 1 0 0 1 0 1 1 0 0 0 0 0 0 0 Overrange
1001 1001 0 0 0 1 1 1 1 1 0 1 0 0 1 0 0 0
1000 1000 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–270 –270 1 111011110010000
< –270 –271 1 1 1 1 0 1 1 1 1 0 0 0 1 0 0 1 Underflow
Measuring Range for Thermocouple: Type E in _F
Table 12-50SIMATIC S5 Format: Measuring Range Type E in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109876543210XEO
> 2192 2193 0 1 0 0 0 1 0 0 1 0 0 0 1 0 0 1 Overflow
2912 2192 0 1 1 0 0 1 0 0 1 1 0 0 0 0 0 0 Overrange
1833 1833 0 0 1 1 1 0 0 1 0 1 0 0 1 0 0 0
1832 1832 0 0 1 1 1 0 0 1 0 1 0 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–454 –454 1 111000111010000
< –454 –455 1 1 1 1 0 1 1 1 1 0 0 0 1 0 0 1 Underflow