Analog Electronic Modules
12-36
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple: Type L in _C
Table 12-55SIMATIC S5 Format: Measuring Range Type L in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109876543210XEO
> 1150 1151 0 0 1 0 0 0 1 1 1 1 1 1 1 0 0 1 Overflow
1150 1150 0 0 1 0 0 0 1 1 1 1 1 1 0 0 0 0 Overrange
901 901 0 0 0 1 1 1 0 0 0 0 1 0 1 0 0 0
900 900 0 0 0 1 1 1 0 0 0 0 1 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–200 –200 1 111100111000000
< –200 –201 1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 1 Underflow
Measuring Range for Thermocouple: Type L in _F
Table 12-56SIMATIC S5 Format: Measuring Range Type L in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109876543210XEO
> 2102 2103 0 0 1 0 0 0 0 1 1 0 1 1 1 0 0 1 Overflow
2102 2102 0 0 1 0 0 0 0 1 1 0 1 1 0 0 0 0 Overrange
1653 1653 0 0 1 1 0 0 1 1 1 0 1 0 1 0 0 0
1652 1652 0 0 1 1 0 0 1 1 1 0 1 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–328 –328 1 111010111000000
< –328 –329 1 1 1 1 0 1 0 1 1 0 1 1 1 0 0 1 Underflow