Loading...
Analog Electronic Modules
12-37
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple: Type N in _C
Table 12-57SIMATIC S5 Format: Measuring Range Type N in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109 8 7 6 543210XEO
> 1550 1551 0 0 1 1 0 0 0 0 0 1 1 1 1 0 0 1 Overflow
1550 1550 0 0 1 1 0 0 0 0 0 1 1 1 0 0 0 0 Overrange
1301 1301 0 0 1 0 1 0 0 0 1 0 1 0 1 0 0 0
1300 1300 0 0 1 0 1 0 0 0 1 0 1 0 0 0 0 0
1 1 0 0 0 0 0 0 0 000001000
0 0 0 0 0 0 0 0 0 00000000 0 Rated range
1 1 1 1 1 1 1 1 1 111111000
270 270 1 1 1 1 0 1 1 110010000
< 270 271 1 1 1 1 0 1 1 1 1 0 0 0 1 0 0 1 Underflow
Measuring Range for Thermocouple: Type N in _F
Table 12-58SIMATIC S5 Format: Measuring Range Type N in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109 8 7 6 543210XEO
> 2822 2823 0 1 0 1 1 0 0 0 0 0 1 1 1 0 0 1 Overflow
2822 2822 0 1 0 1 1 0 0 0 0 0 1 1 0 0 0 0 Overrange
2373 2373 0 1 0 0 1 0 1 0 0 0 1 0 1 0 0 0
2372 2372 0 1 0 0 1 0 1 0 0 0 1 0 0 0 0 0
1 1 0 0 0 0 0 0 0 000001000
0 0 0 0 0 0 0 0 0 00000000 0 Rated range
1 1 1 1 1 1 1 1 1 111111000
454 454 1 1 1 1 0 0 0 111010000
< 454 455 1 1 1 1 0 0 0 1 1 1 0 0 1 0 0 1 Underflow