Analog Electronic Modules
12-38
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Ranges for Thermocouple: Types R, S in _C
Table 12-59SIMATIC S5 Format: Measuring Range Types R, S in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109876543210XEO
> 2019 2020 0 0 1 1 1 1 1 1 0 0 1 0 0 0 0 1 Overflow
2019 2019 0 0 1 1 1 1 1 1 0 0 0 1 1 0 0 0 Overrange
1770 1770 0 0 1 1 0 1 1 1 0 1 0 1 0 0 0 0
1769 1769 0 0 1 1 0 1 1 1 0 1 0 0 1 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–50 –50 1 111111001110000
–51 –51 1 1 1 1 1 1 1 0 0 1 1 0 1 0 0 0 Underrange
–170 –170 1 1 1 1 1 0 1 0 1 0 1 1 0 0 0 0
< –170 –171 1 1 1 1 1 0 1 0 1 0 1 0 1 0 0 1 Underflow
Measuring Ranges for Thermocouple: Types R, S in _F
Table 12-60SIMATIC S5 Format: Measuring Range Types R, S in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109876543210XEO
> 3666 3667 0 1 1 1 0 0 1 0 1 0 0 1 1 0 0 1 Overflow
3666 3666 0 1 1 1 0 0 1 0 1 0 0 1 0 0 0 0 Overrange
3217 3217 0 1 1 0 0 1 0 0 1 0 0 0 1 0 0 0
3216 3216 0 1 1 0 0 1 0 0 1 0 0 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
–1 –1 1 111111111111000
–58 –58 1 111111000110000
–59 –59 1 1 1 1 1 1 1 0 0 0 1 0 1 0 0 0 Underrange
–274 –274 1 1 1 1 0 1 1 1 0 1 1 1 0 0 0 0
< –274 –275 1 1 1 1 0 1 1 1 0 1 1 0 1 0 0 1 Underflow