Analog Electronic Modules
12-39
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Measuring Range for Thermocouple: Type T in _C
Table 12-61SIMATIC S5 Format: Measuring Range Type T in C
Measuring
Units Data Word Range
Range in
_C
(Decimal)
12 11109876543210XEO
> 540 541 0 0 0 1 0 0 0 0 1 1 1 0 1 0 0 1 Overflow
540 540 0 0 0 1 0 0 0 0 1 1 1 0 0 0 0 0 Overrange
401 401 0 0 0 0 1 1 0 0 1 0 0 0 1 0 0 0
400 400 0 0 0 0 1 1 0 0 1 0 0 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
1 1 1 111111111111000
270 270 1 111011110010000
< 270 271 1 1 1 1 0 1 1 1 1 0 0 0 1 0 0 1 Underflow
Measuring Range for Thermocouple: Type T in _F
Table 12-62SIMATIC S5 Format: Measuring Range Type T in F
Measuring
Units Data Word Range
Range in
_F
(Decimal)
12 11109876543210XEO
> 1004 1005 0 0 0 1 1 1 1 1 0 1 1 0 1 0 0 1 Overflow
1004 1004 0 0 0 1 1 1 1 1 0 1 1 0 0 0 0 0 Overrange
753 753 0 0 0 1 0 1 1 1 1 0 0 0 1 0 0 0
752 752 0 0 0 1 0 1 1 1 1 0 0 0 0 0 0 0
1 1 0 000000000001000
0 0 0 00000000000000 0 Rated range
1 1 1 111111111111000
454 454 1 111000111010000
< 454 455 1 1 1 1 0 0 0 1 1 1 0 0 1 0 0 1 Underflow