12.1.6 Analog Value Representation for the Measuring Ranges of the
Analog Output Modules in SIMATIC S5 Format
Introduction
The tables in this section contain the digitized output ranges for the analog output
modules.
Output Ranges for Voltage and Current: " 10 V, " 20 mA
Table 12-63SIMATIC S5 Format: Output Ranges "10 V, "20 mA
Output Range
Units Data Word Range
(Deci-
" 10 V " 20 mA
(Deci-
mal)
11 109 876543210xxxx
0 0 w1205 0 1 0 0 1 0 1 1 0 1 0 1 x x x x Overflow
11.76 23.5156 1204 0 1 0 0 1 0 1 1 0 1 0 0 x x x x Underrange
10.0098 20.0195 1025 0 1 0 0 0 0 0 0 0 0 0 1 x x x x
10.0000 20.000 1024 0 1 0 0 0 0 0 0 0 0 0 0 x x x x Rated
0.00976 0.0195 1 0 0 0 000000001xxxx
range
0 0.000 0 0 0 0 000000000xxxx
–0.0098 –0.0195 –1 1 1 1 111111111xxxx
–10.0000 –20.000 –1024 1 1 0 000000000xxxx
–10.0098 –20.0195 –1025 1 0 1 1 1 1 1 1 1 1 1 1 x x x x Underrange
–11.7578 –23.5156 –1204 1 0 1 1 0 1 0 0 1 1 0 0 x x x x
0 0 v1205 1 0 1 1 0 1 0 0 1 0 1 1 x x x x Underflow