Analog Electronic Modules
12-57
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
12.4 Parameters for Analog Electronic Modules
Parameters for
2AI U Standard Analog Electronic Module
2AI I 2WIRE Standard Analog Electronic Module
2AI I 4WIRE Standard Analog Electronic Module
Table 12-71Parameters for Analog Input Modules U, I Standard
2AI U
Standard
2AI I 2WIRE
Standard
2AI I 4WIRE
Standard
Value Range Default Applicability
Group diagnosis (parameter assignment error,
internal error)
Disable
Enable
Disable Module
Diagnostics: Overflow/underflow Disable
Enable
Disable Module
Diagnostics:
Wire break
2
Diagnostics:
Wire break
Diagnostics:
Wire break
1
Disable
Enable
Disable Channel
Smoothing None
Weak
Medium
Strong
None Channel
Type/range of
measurement
––– ––– Deactivated
5 V
1 to 5 V
10 V
"10 V Channel
––– Type/range of
measurement
––– Deactivated
2WIRE: 4 to
20 mA
2WIRE: 4 to 20
mA
Channel
––– ––– Type/range of
measurement
Deactivated
4WIRE: 4 to
20 mA
4WIRE:
20 mA
2WIRE: 4 to
20 mA
Channel
1
Only in the measuring range 4 to 20 mA
2
Only in the measuring range 1 to 5 V