Analog Electronic Modules
12-58
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Parameters for
2AI U High Feature Analog Electronic Module
2AI I 2/4WIRE High Feature Analog Electronic Module
Table 12-72Parameters for Analog Electronic Modules U, I High Feature
2AI U High Feature
2AI I 2/4WIRE High
Feature
Value Range Default Applicability
Group diagnosis (parameter assignment
error, internal error)
Disable
Enable
Disable Module
Diagnostics: Overflow/underflow Disable
Enable
Disable Module
––– Diagnostics: Wire
break
1
Disable
Enable
Disable Channel
Smoothing None
Weak
Medium
Strong
None Channel
Type/range of
measurement
––– Deactivated
"5 V
1 to 5 V
"10 V
"10 V Channel
––– Type/range of
measurement
Deactivated
4 to 20 mA
"20 mA
4 to 20 mA Channel
Interference frequency suppression Disable
Enable
Disable Module
Run-time calibration Disable
Enable
Disable Module
1
Only in the measuring range 4 to 20 mA