Analog Electronic Modules
12-59
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Parameters for
2AI U High Speed analog electronic module
2AI I 2WIRE High Speed analog electronic module
2AI I 4WIRE High Speed analog electronic module
Table 12-73Parameters for U, I, and High Speed Analog Input Modules
2AI U High
Speed
2AI I 2WIRE
Standard
2AI I 4WIRE
High Speed
Value Range Default Applicability
Group diagnosis (parameter assignment error,
internal error)
Disable
Enable
Disable Module
Diagnostics: Overflow/underflow Disable
Enable
Disable Module
––– Diagnostics:
Wire break
Diagnostics:
Wire break
Disable
Enable
Disable Channel
Smoothing None
Weak
Medium
Strong
None Channel
Type/range of
measurement
––– ––– Deactivated
"10 V
"5 V
" 2.5 V
1 to 5 V
"10 V Channel
––– Type/range of
measurement
––– Deactivated
4 to 20 mA
0 to 20 mA
4 to 20 mA Channel
––– ––– Type/range of
measurement
Deactivated
4 to 20 mA
0 to 20 mA
" 20 mA
4 to 20 mA Channel
Note
If you deactivate a channel of the High Speed module, you do not achieve any
speed advantage on account of the measuring procedure used.