Table 12-74Parameters for Analog Input Modules RTD, TC
2AI RTD
Standard
2AI TC
Standard
2AI TC High
Feature
Value Range Default Applica-
bility
Group diagnosis (parameter assignment
error, internal error)
Disable
Enable
Disable Module
Diagnostics: Overflow/underflow Disable
Enable
Disable Module
Diagnos-
tics: Wire
break
2
Diagnostics: Wire break
check
1
Disable
Enable
Disable Channel
Smoothing None
Weak
Medium
Strong
None Channel
Temperature
unit
Celsius
Fahrenheit
Celsius Module
––– Reference
junction
––– None
RTD
None Channel
––– Reference
junction
None
Yes (i.e. internal)
None Channel
––– Reference
junction
number
––– None
1 to 8 (in the case of the
IM151-1 STANDARD, IM151-1
None Module
FO STANDARD)
1 (in the case of the IM151-1
BASIC, IM151-1 HIGH
FEATURE)
Type/
range of
measure-
ment
––– Deactivated
150 ohms
300 ohms
600 ohms
Pt100 Climatic
Ni100 Climatic Range
Pt100 Standard
Ni100 Standard
Pt100
Standard
Channel