Analog Electronic Modules
12-62
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Parameters for
2AI RTD High Feature analog electronic module
Table 12-75Parameters for 2AI RTD High Feature Analog Electronic Module
Parameters
Value Range Default Applicability
Group diagnosis Disable
Enable
Disable Module
Diagnostics: Overflow/underflow Disable
Enable
Disable Module
Diagnostics: Wire break Disable
1
Enable
Disable Channel
Smoothing None
Weak
Medium
Strong
None Channel
Temperature unit Celsius
Fahrenheit
Celsius Module
Type of measurement Deactivated
Four-conductor resistor
Three-conductor resistor
Two-conductor resistor
Four-conductor thermal
resistor
Three-conductor thermal
resistor
Two-conductor thermal
resistor
Four-conductor
thermal resistor
Channel
Temperature Coefficient Pt 0.003850
Pt 0.003916
Pt 0.003902
Pt 0.003920
Pt 0.003851
Ni 0.006180
Ni 0.006720
Cu 0.00427
Pt 0.003851 Channel