Analog Electronic Modules
12-95
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 12-83Terminal Assignment of the 2AI I 2/4WIRE High Feature
View RemarksTerminal Assignment
M
1
M
0
2
3
4
6
7
8
15
M
1+
M
0+
TM-E15S24-01 and 2AI I 2/4WIRE High Feature
(Alternative terminal assignment for 2WIRE)
24 VDC+24 VDC+
2 conductors
CH0 CH1
mA
24 VDC24 VDC
Two-wire measuring transducer
Channel 0: Terminals 1 to 4
Channel 1: Terminals 5 to 8
M+ : Input signal “–”
M : Connect to 24 VDC
24 VDC+: Input signal+
Two-wire measuring
transducers are supplied by
means of the measuring
circuits.
Mixing two-wire and four-wire
measuring transducers is
permitted.
To support isolation between
the channels, use an external
supply to feed one of the
measuring transducers.
M
1
M
0
2
3
4
6
7
8
15
M
1+
M
0+
mA
TM-E15S26-A1 and 2AI I 2/4WIRE High Feature
24 VDC+24 VDC+
4 conductors
CH0 CH1
mA
24 VDC24 VDC
Four-wire measuring transducer
AUX1
A
4
A
3
A
8
A
7
AUX1
AUX1
AUX1
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+ : Input signal +
M: Input signal “–”
24 VDC+: Power supply for
four-wire measuring transducer
24 VDC: Return circuit for
measuring transducer supply
It is possible to supply four-wire
measuring transducers by
means of the module.
To support isolation between
the channels, use an external
supply to feed one of the
measuring transducers.