EasyManua.ls Logo

Siemens ET 200S - Page 452

Siemens ET 200S
564 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Electronic Modules
12-96
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
Table 12-83Terminal Assignment of the 2AI I 2/4WIRE High Feature
View RemarksTerminal Assignment
M
1
M
0
2
3
4
6
7
8
15
M
1+
M
0+
TM-E15S26-A1 and 2AI I 2/4WIRE High Feature
(Alternative terminal assignment for
2WIRE)
24 VDC+24 VDC+
2 conductors
CH0 CH1
mA
24 VDC24 VDC
Two-wire measuring transducer
AUX1
A
4
A
3
A
8
A
7
AUX1
AUX1
AUX1
Channel 0: Terminals 1 to A3
Channel 1: Terminals 5 to A7
M+ : Input signal “–”
M : Connect to 24 VDC
24 VDC+: Input signal +
Two-wire measuring
transducers are supplied by
means of the measuring
circuits.
Mixing two-wire and four-wire
measuring transducers is
permitted.
To support isolation between
the channels, use an external
supply to feed one of the
measuring transducers.
Block Diagram
ADC
M
ANA
24 V
L+
1M
1
2
5
6
7
3
8
4
P1
P2
MUX
Backplane bus
ET 200S
backplane bus
interface module
Current limit
Figure 12-13 Block Diagram of the 2AI I 2/4WIRE High Feature

Table of Contents