4 IQ-SENSE
13-9
Distributed I/O System ET 200S
EWA 4NEB 780 6024-02 07
13.2 Control and Feedback Interface (PIQ/PII)
You can configure the address space of the control and feedback interfaces of the
4 IQ-SENSE. You can choose between Standard and Enhanced.
Standard Features
The 4 IQ-SENSE occupies 4 bits in the feedback interface.
The 4 IQ-SENSE can be grouped in a single byte. Two 4 IQ-SENSE modules
can be grouped in each byte. See also Section 6.1.
You can evaluate the circuit state of each channel using the feedback interface.
Enhanced Features
The 4 IQ-SENSE occupies one byte in the control interface and one in the
feedback interface.
You can use the control interface to specify the sensitivity and distance values
for each channel (IntelliTeach via “IQ-SENSE Opto” FB) and execute teach-in.
You can use the feedback interface to evaluate the acquired sensitivity and
distance values (switching threshold) and the circuit state for each channel.
Prerequisites:
You can use the “IQ-SENSE Opto” function block. The FB facilitates easy
access to the control and feedback interface.
Please note that in this case PII equals PIQ.
You can download the function block and the relevant product information on
the Internet at http://www.ad.siemens.de/csi_e/gsd.
Configuring the Address Space
Address
Space
With STEP7 as of V5.1,
ServicePack 3
With STEP7 as of V4.02 or COM
PROFIBUS or other
configuration software
Standard In the hardware catalog of From the DDB file, choose
HWCONFIG, choose
4IQ-SENSE Opto S.
S 6ES7 138-4GA00-0AB0
IQ-SENSE Opto.
Enhanced In the hardware catalog of From the DDB file, choose
HWCONFIG, choose
4IQ-SENSE Opto E.
E 6ES7 138-4GA00-0AB0
IQ-SENSE Opto.