Article number 6DL1155-6AU00-0PM0
Address space per module, max.
256 byte
Address space per station
Address space per station, max.
1 440 byte; 1 440 bytes R1 and S1 without CiR,
otherwise 1 000 bytes
Hardware con󹪝guration
Integrated power supply Yes; 24 V DC
Rack
Modules per rack, max.
56; 56 slots for I/O modules + server module (width
without IM ≤ 1.3 m)
Time stamping
Accuracy 1 ms; In compliance with the supplementary con‐
ditions described in the Equipment Manual
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
Number of ports
2; via BusAdapter
integrated switch
Yes
BusAdapter (PROFINET)
Yes; Compatible BusAdapters: BA 2x RJ45, BA 2x FC,
BA 2x LC, BA LC/RJ45, BA LC/FC, BA VD
Protocols
PROFINET IO Device
Yes
Open IE communication
Yes
Media redundancy
Yes; as MRP client
Interface types
RJ 45 (Ethernet)
Transmission procedure
PROFINET with 100 Mbit/s full duplex (100BASE-TX)
100 Mbps
Yes; PROFINET with 100 Mbit/s full duplex
(100BASE-TX)
Autonegotiation
Yes
Autocrossing
Yes
Redundancy mode
Media redundancy
MRP
Yes
Open IE communication
TCP/IP
Yes
SNMP
Yes
LLDP
Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
RUN LED
Yes; green LED
Technical speci󹪝cations
8.1 Technical speci󹪝cations
IM 155-6 PN HA
36 Equipment Manual, 09/2021, A5E39262148-AE