Diagnostic messages
A
A.1 Diagnostics alarms
Diagnostic messages
For each diagnostic event, a diagnostic message is output and the ER LED 󹪞ashes on the module.
The diagnostic messages can, for example, be read from the diagnostic bu󹪜er of the CPU.
There can be more than one diagnostics alarm at the same time.
Table A-1 Diagnostic messages, their meaning and possible remedies
Diagnostics mes‐
sage
Channel
error
type
(CET)
Exten‐
ded chan‐
nel error
type
(CET)
Assignment Meaning Remedy
Con󹪝guration error:
Station Stop – No
server module
0x0602 0x0693 Con󹪝gura‐
tion
No server module was
present during power-up of
an ET 200SP HA station.
Verify that the server module is
correctly installed in the rack.
Con󹪝guration error:
Module parameter
<potential group> er‐
rors or incorrect ter‐
minal block present
in real slot <slot>
0x0602 0x0691 Con󹪝gura‐
tion
The installed terminal block
does not match the con󹪝gu‐
ration.
Ensure that a matching termi‐
nal block is installed.
Con󹪝guration error:
Permissible back‐
plane bus size excee‐
ded
0x0602 0x0698 Con󹪝gura‐
tion
The total width of the instal‐
led modules exceeds the per‐
missible assembly length of
1300 mm.
Verify that the backplane bus
con󹪝guration does not exceed
the permissible size.
The server module must be the
last module plugged in (high‐
est permissible slot number:
58).
Con󹪝guration error:
Incorrect backplane
bus con󹪝guration in
slot <slot>
0x0602 0x0699 Con󹪝gura‐
tion
The maximum current de‐
mand of all plugged-in mod‐
ules exceeds 2100 mA.
The accompanying <slot> val‐
ue indicates the slot causing
the error.
Check the con󹪝guration of the
ET 200SP HA.
Con󹪝guration error:
Impermissible bus
adapter on interface
module
0x0602 0x069C Con󹪝gura‐
tion
The installed bus adapter
does not match the con󹪝gu‐
ration.
Verify that a matching bus
adapter is installed.
Con󹪝guration error:
No server module
0x0602 0x069E Con󹪝gura‐
tion
The server module is pulled
during operation of an
ET 200SP HA station.
Ensure that the server module
is correctly installed in the rack.
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE 45